Memory area for GPIO, LED, and system information

Use the addresses in this memory area when the FP-I4C unit is used together with general-purpose input/output (GPIO) and LEDs.

Memory areas that cannot be written to are marked read-only.

Address

Description

Read-only

33088 (16#8140)

Status of F1, F2 and all LEDs as 16-bit data.

Bit 0: PWR LED, bit 1: CON LED, bit 2: USR LED, bit 3: MEM LED, bit 4: USB1 LED, bit 5: USB2 LED, bit 6: COM1 LED, bit 7: COM2 LED, bit 8: F1 input, bit 9: F2 input, bit 10: reset tact switch (top side, inside housing), bit 11: power failure

33089 (16#8141)

Status PWR LED, 1: on, 0: off

Turns on if the power supply is turned on.

33090 (16#8142)

Status CON LED, 1: on, 0: off

This LED can be used for any purpose.

 

33091 (16#8143)

Status USR LED, 1: on, 0: off

This LED can be used for any purpose.

 

33092 (16#8144)

Status MEM LED, 1: on, 0: off

Turns on when data is written to the USB flash drive.

33093 (16#8145)

Status USB1 LED, 1: on, 0: off

Turns on when a device is connected to USB port 1.

33094 (16#8146)

Status USB2 LED, 1: on, 0: off

Turns on when a device is connected to USB port 2.

33095 (16#8147)

Status TX1 LED, 1: on, 0: off

Blinks quickly when communication via COM1 RS232 is active.

33096 (16#8148)

Status TX2 LED, 1: on, 0: off

Blinks quickly when communication via COM2 RS232/RS485 is active.

33097 (16#8149)

Status F1 input, 1: on, 0: off

Normally closed (normal state: 1). To turn this input to TRUE, simply connect it to GND (G1).

33098 (16#814A)

Status F2 input, 1: on, 0: off

Normally closed (normal state: 1). To turn this input to TRUE, simply connect it to GND (G1).

33099 (16#814B)

Status RESET (reset tact switch), 1: on, 0: off

33100 (16#814C)

Status PFAIL (power failure), 1: on, 0: off

33104 (16#8150)

Device start time stamp in seconds, first word

This is a value in Control FPWIN Pro7's DATE_AND_TIME format (seconds since 1/1/2001). To convert the data into a UNIX time stamp (seconds since 1/1/1970), add 978307200 seconds.

33105 (16#8151)

Device start time stamp in seconds, second word

33106 (16#8152)

Reserved.

 

33107 (16#8153)

Reserved.

 

33108 (16#8154)

Device shutdown time stamp in seconds, first word

This is a value in Control FPWIN Pro7's DATE_AND_TIME format (seconds since 1/1/2001). To convert the data into a UNIX time stamp (seconds since 1/1/1970), add 978307200 seconds.

33109 (16#8155)

Device shutdown time stamp in seconds, second word

33110 (16#8156)

Reserved.

 

33111 (16#8157)

Reserved.

 

33112 (16#8158)

Device start before last time stamp in seconds, first word

This is a value in Control FPWIN Pro7's DATE_AND_TIME format (seconds since 1/1/2001). To convert the data into a UNIX time stamp (seconds since 1/1/1970), add 978307200 seconds.

33113 (16#8159)

Device start before last time stamp in seconds, second word

33114 (16#815A)

Reserved.

 

33115 (16#815B)

Reserved.

 

33116 (16#815C)

Device shutdown before last time stamp in seconds, first word

This is a value in Control FPWIN Pro7's DATE_AND_TIME format (seconds since 1/1/2001). To convert the data into a UNIX time stamp (seconds since 1/1/1970), add 978307200 seconds.

33117 (16#815D)

Device shutdown before last time stamp in seconds, second word

33118 (16#815E)

Reserved.

 

33119 (16#815F)

Reserved.

 

33120 (16#8160)

Device temperature (inside CPU) in 0.1°C

Modified on: 2024-10-15Feedback on this pagePanasonic hotline