WORD
Clock/calendar activation (bit 15) and seconds correction (bit 0)
Setting bit 15 to TRUE (16#8000) activates the clock and calendar values specified using sys_wClockCalendarMinSec, sys_wClockCalendarDayHour, sys_wClockCalendarYearMonth, or sys_wClockCalendarDayOfWeek.
The following settings do not apply to FP-Sigma and FP-e.
Setting bit 0 to TRUE (16#1) sets the number of seconds to 0 and rounds the number of minutes:
0s–29s: The number of minutes remains unchanged.
30s–59s: The number of minutes is incremented by 1.
Use the MOVE instruction to set bits 0 and 15 to TRUE. After the instruction has been executed, bits 0 and 15 are reset to FALSE.
FP-X: only available if the FP-X master memory cassette is installed.