sys_wMewnetFError1StationNumber_17_32

Group

MEWNET-F (remote I/O)

Data type

WORD

Name

MEWNET-F error 1 at station number 17–32

The data register indicates the station number of the MEWNET-F slave at which an error occurred. Bit nos. 0–15 correspond to station nos. 17–32.

For sys_wMewnetFErrorSelection = 16#0, 16#1, 16#2, 16#3 (masters 1–4): hardware error

For sys_wMewnetFErrorSelection = 16#100, 16#101, 16#102, 16#103 (masters 1–4): I/O verify error

Modified on: 2019-12-14Feedback on this pagePanasonic hotline