The names for the interrupts are entered automatically by ascending number, e.g. GR_Interrupt0, GR_Interrupt1...
Particularities of GR/GR7 type interrupts in comparison to Control FPWIN Pro7 interrupts:
No automatic ICTL init code should be generated for these POUs by the compiler. They have to be activated by an explicit ICTL.
An automatic ICTL init code is generated only for IEC interrupt POUs by the compiler.