FP_SYSTEM_MONITOR_UNIT_ERROR_DUT

This DUT can be used with the following instruction(s): FP_SYSTEM_MONITOR_READ

Elements of the DUT (identifiers):

bUnitErrorCpuComPort (BOOL)

TRUE: CPU COM port error, FALSE: No error

bUnitErrorCpuEthernetPort (BOOL)

TRUE: CPU Ethernet port error, FALSE: No error

wUnitErrorSlot_1_16 (WORD)

Error slot 1–16

Bit 0 = Slot 1, Bit 15 = Slot 16

wUnitErrorSlot_17_32 (WORD)

Error slot 17–32

Bit 0 = Slot 17, Bit 15 = Slot 32

wUnitErrorSlot_33_48 (WORD)

Error slot 33–48

Bit 0 = Slot 33, Bit 15 = Slot 48

wUnitErrorSlot_49_64 (WORD)

Error slot 49–64

Bit 0 = Slot 49, Bit 15 = Slot 64

wUnitErrorFirstTime_YYMM (WORD)

First occurrence of error in BCD time format Year, Month

wUnitErrorFirstTime_DDHH (WORD)

First occurrence of error in BCD time format Day, Hour

wUnitErrorFirstTime_MMSS (WORD)

First occurrence of error in BCD time format Minute, Second