Overview of Logging function

Specifications

Item

Specifications

 

FP7

FP0H

FP-XH

Max. number of records

1,000,000 records

60000 records

40000 records

Max. number of generated files per log folder

2000

2000

1500

Max. number of variables

Max. 500 variables (5002000 words) / 1 record

Max. 182 variables (182–2000 words) / 1 record

Max. 182 variables (182–1500 words) / 1 record

Buffer memory

Shared with the trace function.

Can be divided into max. 16 (LOG0–LOG15) areas for use.

Can be divided into max. 4(LOG0–LOG3) areas for use.

Logging trigger condition

  • Bit device ON: Logging is executed when the condition is met at the end of a scan.

  • Interval: Hour, minute, second

  • Time: Per minute, Per hour, Every day, Every week, Every month, Every year
  • Instruction (FP_LOGTRACE_SAMPLE) : Executes an instruction with an arbitrary condition and starts logging.

File completion condition (Logging stop trigger condition)

  • Bit device ON: Use it together with the DF instruction to turn ON only for one scan.

  • Time: Per minute, Per hour, Every day, Every week, Every month, Every year
  • Max. number of records

File format

Data is saved in CSV format.

Arbitrary comments can be given.

The upper limit of the capacity on the file system is 4 GB.

Image of logging function

Related topics: