Errors when operation was executed using data recording instructions

This section describes the situations and countermeasures when data recording starts or stops, or sampling trigger operation is performed with instructions in user programs.

Situation or error message

Situation Countermeasures

ERROR LED turns on.

A self-diagnostic error such as an operation error occurs.

When an operation error occurs in the address of FP_LOGTRACE_START, FP_LOGTRACE_STOP, or FP_LOGTRACE_SAMPLE instruction, check the followings.

An operation error occurred in the address of FP_LOGTRACE_START or FP_LOGTRACE_STOP

The instruction may have been executed for an unregistered LOG number.

Check if the settings match the LOG number for which the instruction is executed.

There is a possibility that no SD card is inserted, or the card cover is open.

Check if an SD card is inserted, and close the card cover.

An operation error occurred in the address of FP_LOGTRACE_SAMPLE instruction.

The instruction was executed for a LOG number but Instruction (FP_LOGTRACE_SAMPLE) has not been selected as a trigger condition for this LOG number.

Check if the settings of sampling trigger match the LOG number for which the instruction is executed.

Data recording is not executed with FP_LOGTRACE_SAMPLE instruction.

There is a possibility that the LOG number does not match.

Check if the settings match the LOG number for which the instruction is executed.