Input (X) flags of MCU unit

16 I/Os for X are allocated. I/O addresses are determined depending on the installation location and the I/O allocations of the other units.

Input signal

Name

Description (0: OFF, 1: ON)

Effective operation mode

COM 1

COM 2

X0

X2

Reception done flag

When the MCU completes the data reception, it turns on.

When waiting for the end of data reception: 0

When data reception completed: 1

Program controlled communication

X1

X3

PLC data reception done flag

When F161_MRCV is completed, it is set/reset.

Reading completed: 1

Data not yet read: 0 1)

X4

X5

Transmission done flag

When transmission is available: 1

During transmission: 0 2)

When transmission is completed: 1

X6

X7

Reception error

When F161_MRCV is completed, it is set/reset.

Errors exist in the data read: 1

No error exists in the data read: 0 1)

X8

X9

CTS signal monitor

Status of the CTS signal sent from the device being communicated with.

Transmission from MCU is possible: 0

Transmission from MCU is not possible: 1

The RTS signal from the MCU is controllable by Y18 and Y19.

Effective only when setting the RS/CS to be valid and using the communication block AFP2803

XA

XC

Latest reception error

Set when an error occurs during the reception of data by the MCU

No reception error: 0

Reception error: 1

The details of the reception error can be confirmed by reading them to the PLC using the F161_MRD_STATUS instruction.

Check X6/X7 to see whether or not there are errors in each receive buffer during multiple reception.

Program controlled communication (Reception)

XB

XD

Setting error

Operation mode switch setting error

Usage restrictions for the unit

All operation modes

XE

XF

CH reset done

Communication channels can be reset by turning on Y1E or Y1F. The flag is reset upon completion.

At completion: 1

When Y1E/Y1F is off: 0

Program controlled communication

1)

After the F161_MRCV instruction has been executed, this flag is effective until one of the following instructions is executed.

  • END instruction (Beginning of scan)

  • F161_MRCV instruction

  • Partial input instruction F143_IORF

2)

When the transmission is completed within one scan, it may not be 0.

Related topics: