There are two operation recording options: Operation list (Alarms History) and Operation chart (Gantt Chart).
The two operation recording options are configured the same way apart from the option Event names, which is only available for Operation list (Alarms History).
General
Option |
Default setting |
Setting range |
Description |
---|---|---|---|
Application |
Operation list (Alarms History) |
Operation list (Alarms History)/Operation chart (Gantt Chart) |
Type of operation recording |
Buffer size (records) |
500 |
1–3000 |
Max. number of records to be saved in the buffer |
Folder name on SD card |
OPH + configuration number |
OPH0–OPH7 |
Folder name on the SD card |
File name on SD card |
– |
User-defined |
Name of the CSV file. The file name is used if you save the record buffer into a CSV file on the SD card. To save the CSV file, use the instruction FP_OPERATION_RECORDING_WRITE_TO_SD or press the CSV button of the Alarms History or Gantt Chart widget on the web page created with Control Web Creator. |
Files per SD card folder |
128 |
1–128 |
Max. number of files to be created per SD card folder |
If exceeded |
Delete oldest file |
Fixed |
Operation
Option |
Default setting |
Setting range |
Description |
---|---|---|---|
Start when changing to RUN mode |
Activated |
Activated/Deactivated |
Starting method for the operation recording function. If deactivated, start the operation recording function with the instruction FP_OPERATION_RECORDING_START or the Start button in the operation recording editor or the start button of the Alarms History or Gantt Chart widget on the web page created with Control Web Creator. |
When buffer is full |
Pause recording |
Pause recording/Delete oldest record |
Action to take when the buffer is full |
Language
Option |
Default setting |
Setting range |
Description |
---|---|---|---|
Count |
Language 1 |
Language 1/Language 2 |
Alternative language to be used for the event names and data names |
Language name 1/2 (optional) |
– |
User-defined |
Name of the language used, e.g. "German" or "Japanese". The language name appears in the operation recording editor in the respective column where you enter the name for the recorded data. |
Event names (only for Operation list (Alarms History))
Option |
Default setting |
Setting range |
Description |
---|---|---|---|
Triggered |
Trig |
User-defined |
Text to appear on the parts of a web page created with Control Web Creator when a variable or an address is in a specified alarm status |
Recovered |
Rcv |
User-defined |
Text to appear on the parts of a web page created with Control Web Creator when a variable or an address is in a specified alarm status |
Acknowledged |
Ack |
User-defined |
Text to appear on the parts of a web page created with Control Web Creator when a variable or an address is in a specified alarm status |