Unit_AnalogInput_FP7_TC8

Function to read from an FP7-TC8 unit.

This function reads converted digital data from the analog input channel specified by iSlotNumber. The converted digital values are stored per channel in the output variables iInChannel0 to iInChannel7.

Parameters

Input

iSlotNumber (INT)

Set the slot number of the analog unit. The FP7 CPU has slot number 0.

Output

iInChannel0iInChannel7 (INT)

Returns the converted digital data from the analog unit by channel.

Values:

Voltage and current input:
  • For -10 to +10V: -31250 to +31250
  • For 0 to 10V, 0 to 5V, 0 to 20 mA: 0 to 31250
  • For 1 to 5 V, 4 to 20 mA: 0 to 25000

Thermocouple input:

Type

Analog value

Digital value (INT)

K1

-115°C or less

-1150

+615°C or more

+6150

K2

-215°C or less

-2150

+1385°C or more

+13850

J1

-115°C or less

-1150

+415°C or more

+4150

J2

-215°C or less

-2150

+ 1215°C or more

+12150

T

-285°C or less

-2850

+415°C or more

+ 4150

N

-285°C or less

-2850

+ 1315°C or more

+ 13150

R

-15°C or less

-150

+1775°C or more

+17750

S

-15°C or less

-150

+1775°C or more

+ 17750

B

-15°C or less

-150

1835°C or more

+ 18350

E

-285°C or less

-2850

+1015°C or more

+ 10150

PL

-15°C or less

-150

+1405°C or more

+ 14050

WRe5-26

-15°C or less

-150

+ 2330°C or more

+ 23300