Unit_AnalogInput_FP7_TC8Function to read from an FP7-TC8 unit.

This function reads converted digital data from the analog input channel specified by iSlotNumber. The converted digital values are stored per channel in the output variables iInChannel0 to iInChannel7.
Input
Set the slot number of the analog unit. The FP7 CPU has slot number 0.
Output
Returns the converted digital data from the analog unit by channel.
Values:
Thermocouple input:
Type |
Analog value |
Digital value (INT) |
|---|---|---|
K1 |
-115°C or less |
-1150 |
+615°C or more |
+6150 |
|
K2 |
-215°C or less |
-2150 |
+1385°C or more |
+13850 |
|
J1 |
-115°C or less |
-1150 |
+415°C or more |
+4150 |
|
J2 |
-215°C or less |
-2150 |
+ 1215°C or more |
+12150 |
|
T |
-285°C or less |
-2850 |
+415°C or more |
+ 4150 |
|
N |
-285°C or less |
-2850 |
+ 1315°C or more |
+ 13150 |
|
R |
-15°C or less |
-150 |
+1775°C or more |
+17750 |
|
S |
-15°C or less |
-150 |
+1775°C or more |
+ 17750 |
|
B |
-15°C or less |
-150 |
1835°C or more |
+ 18350 |
|
E |
-285°C or less |
-2850 |
+1015°C or more |
+ 10150 |
|
PL |
-15°C or less |
-150 |
+1405°C or more |
+ 14050 |
|
WRe5-26 |
-15°C or less |
-150 |
+ 2330°C or more |
+ 23300 |
This command description provides basic hardware documentation only. For detailed technical information, consult the manual:
FP7 Thermocouple Multi-analog Input Unit/FP7 RTD Input Unit User's Manual