Unit_AnalogOutput_FP7_DA4H

Function block to write to an FP7-DA4H unit.

This function writes digital data to the analog output channels of the analog unit. The digital values to be converted and output as analog values are specified at iOutChannel0 to iOutChannel3.

Parameters

Input

iSlotNumber (INT)

Set the slot number of the analog unit. The FP7 CPU has slot number 0.

Output

iOutChannel00 to iOutChannel03 (INT)

Set the digital value to be converted and output by the analog unit.

Values:
  • For -10 to +10V: -31250 to +31250
  • For 0 to 10V, 0 to 5V, 0 to 20 mA: 0 to 31250
  • For 1 to 5 V, 4 to 20 mA: 0 to 25000
bErrorChannel0 to bErrorChannel3 (BOOL)

Channel status: TRUE if there is an error.

Tip

This command description provides basic hardware documentation only. For detailed technical information, consult the manual:

FP7 Analog Output Unit User's Manual

Related topics:

Modified on: 2024-02-26Feedback on this pagePanasonic hotline